Search found 10 matches

by Ricky.Glenn
Mon Jan 25, 2010 10:13 pm
Forum: Nordyne Service & Repair
Topic: Intertherm FEH 015HA-03 Blower will not start
Replies: 20
Views: 17359

Re: Intertherm FEH 015HA-03 Blower will not start

Robert The xfmr at the furnace has 24 vac when measured between the red wire going to the t-stat and the black wire going to the sequencer. There is 240 on the primary side. I haven't checked the xfmr on the AC yet. But I will and will let you know. With the t-stat set to HG, auto and set to demand ...
by Ricky.Glenn
Sun Jan 24, 2010 4:28 pm
Forum: Nordyne Service & Repair
Topic: Intertherm FEH 015HA-03 Blower will not start
Replies: 20
Views: 17359

Re: Intertherm FEH 015HA-03 Blower will not start

Robert

As you suggested, I tried the t-stat in HG ans it did not correct the problem. With the jumper removed, the blower will come on when the t-stat is set to heat, and fan set to on.

Suggestions?

I received the relay and will install it.

Thanks

Ricky
by Ricky.Glenn
Sun Jan 17, 2010 9:42 pm
Forum: Nordyne Service & Repair
Topic: Intertherm FEH 015HA-03 Blower will not start
Replies: 20
Views: 17359

Re: Intertherm FEH 015HA-03 Blower will not start

Robert There is an RH and RC wire, and they are connected to two separate transformers. However, with the jumper removed, the blower will not come on when the t-stat is set to heat, fan auto, and temperature set to demand heat. With the jumper removed, the blower will come on when the t-stat is set ...
by Ricky.Glenn
Sat Jan 16, 2010 10:23 pm
Forum: Nordyne Service & Repair
Topic: Intertherm FEH 015HA-03 Blower will not start
Replies: 20
Views: 17359

Re: Intertherm FEH 015HA-03 Blower will not start

Robert Thank you for the response. I will order the relay. The non OEM Honeywell R8222D relay installed is sticking. Regarding the thermostat: I replaced the thermostat approximately 6 weeks ago. The previous thermostat was wired the same way, RC and RH jumped. The thermostat I replaced had been in ...
by Ricky.Glenn
Thu Jan 14, 2010 11:26 pm
Forum: Nordyne Service & Repair
Topic: Intertherm FEH 015HA-03 Blower will not start
Replies: 20
Views: 17359

Re: Intertherm FEH 015HA-03 Blower will not start

Hi Robert The blower work does work, with the thermostat fan switch set to both auto and on, with the jumper installed. The blower does not work in auto with the jumper removed. Only the RH wire is connected to something at furnace. To the best of my recollection the RH wire goes to a small terminal...
by Ricky.Glenn
Wed Jan 13, 2010 10:20 pm
Forum: Nordyne Service & Repair
Topic: Intertherm FEH 015HA-03 Blower will not start
Replies: 20
Views: 17359

Re: Intertherm FEH 015HA-03 Blower will not start

Hi Robert, I received and replaced the sequencer. That was definitely a portion of my problem. The old sequencer fell apart in my hand. In regards to the wiring of the thermostat. As stated previously, I am using a non programmable hunter thermostat that requires 2 AA batteries. The system has both ...
by Ricky.Glenn
Fri Jan 01, 2010 3:40 pm
Forum: Nordyne Service & Repair
Topic: Intertherm FEH 015HA-03 Blower will not start
Replies: 20
Views: 17359

Re: Intertherm FEH 015HA-03 Blower will not start

Robert I checked the voltages and determined the motor was not getting power. A bit more troubleshooting determined that one of the large fuses was blown. I replaced the fuse and corrected the problem. Thank You The furnace now heats the home, but obviously needs maintenance. I have owned the home f...
by Ricky.Glenn
Thu Dec 31, 2009 8:55 am
Forum: Nordyne Service & Repair
Topic: Intertherm FEH 015HA-03 Blower will not start
Replies: 20
Views: 17359

Re: Intertherm FEH 015HA-03 Blower will not start

Robert

I will check this afternoon. Thanks
by Ricky.Glenn
Thu Dec 31, 2009 8:31 am
Forum: Nordyne Service & Repair
Topic: Intertherm FEH 015HA-03 Blower will not start
Replies: 20
Views: 17359

Re: Intertherm FEH 015HA-03 Blower will not start

The blower did not start and run when I set t-stat to call for heat and spun the blower wheel in direction of rotation.
by Ricky.Glenn
Wed Dec 30, 2009 11:48 pm
Forum: Nordyne Service & Repair
Topic: Intertherm FEH 015HA-03 Blower will not start
Replies: 20
Views: 17359

Intertherm FEH 015HA-03 Blower will not start

I have an Intertherm FEH 015HA-03 manufactured 31 Oct 1988. The heater was working fine. It had been running for a couple of hours because I was replacing the back door on the mobile home. The heater cut off. I though the temperature on the thermostat had been reached. However, the heater did not tu...