Search found 4 matches

by seanmwalls
Wed Aug 18, 2010 9:13 pm
Forum: Nordyne Service & Repair
Topic: Nordyne FT3BA060KA - Contactor Problem?
Replies: 7
Views: 3061

Re: Nordyne FT3BA060KA - Contactor Problem?

That would be greatly appreciated! Thank you again for your help!
by seanmwalls
Tue Aug 17, 2010 6:15 pm
Forum: Nordyne Service & Repair
Topic: Nordyne FT3BA060KA - Contactor Problem?
Replies: 7
Views: 3061

Re: Nordyne FT3BA060KA - Contactor Problem?

The wire coming out of T1 appears to have been the problem. I have removed it and patched over to the common and things are running normally again. Now it looks like I'll need to find a replacement board before winter hits! Thanks for your help.
by seanmwalls
Fri Aug 13, 2010 9:09 am
Forum: Nordyne Service & Repair
Topic: Nordyne FT3BA060KA - Contactor Problem?
Replies: 7
Views: 3061

Re: Nordyne FT3BA060KA - Contactor Problem?

Thanks for the info. When I measure each seperately, I get 1 lead with a 24 VAC reading and the other has a 13 VAC reading. Neither of the leads is 0 VAC. Each of these wires connects right into the control board. I measured the voltage at the transformer (inside the house in the blower housing) and...
by seanmwalls
Thu Aug 12, 2010 9:51 pm
Forum: Nordyne Service & Repair
Topic: Nordyne FT3BA060KA - Contactor Problem?
Replies: 7
Views: 3061

Nordyne FT3BA060KA - Contactor Problem?

Hello, I have a Nordyne FT3BA060KA which does not start when the thermostat calls for cold. I believe it may be either the contactor or the control board. Based on other posts, I measured voltage at each of the wires that attach to the coil. When 1 lead is on the terminal and 1 on the ground, I get ...