Leaking water

Questions about repairs and parts for Nordyne furnaces, air conditioners and heat pumps for manufactured homes including Intertherm, Mac and Miller brands. Click here for Nordyne parts.

Moderators: Greg, Mark

Locked
jess214

I have a Intertherm model E2EB-012HA. Whenever the a/c is turned on water is leaking out from the right control panel cover. Does anybody know what could cause this?
User avatar
Robert
Moderator
Posts: 6413
Joined: Wed Feb 28, 2007 12:07 am
Location: Tennessee

Drip pan under a-coil overflowing, water being drawn out of drip pan, water being pulled off the a-coil surface, drain line being clogged up, drip pan leaking.


Make sure a-coil is clean and fins not damaged and make sure air is being pulled through the coil and not over and around it.


Leave unit off and fill drip pan to check for leaks. Also check for full drainage from drainline.



Take care and best wishes,
Robert